Do I have to wire "home run" cable harnesses for MX system or can I daisy chain from one flasher module to the next?

This article discusses the LED wiring options for MX systems.

Product applicability

The following products are discussed in this article:

  • MX Series: R920-MX, R829-MX, R247-MX, CHEVRON-MX and WWD-MX

MX flasher modules come in four different options:

  1. RRFB
  2. Beacon
  3. LED Sign
  4. Chevron

These flasher modules can be wired two different ways:

  1. One harness per flasher module terminated to the power module on the pole (solar or AC); known as a "home run" or what we call a "centralized approach". We recommend the centralized approach.
  2. A second flasher module can be terminated to the first flasher module on the pole, known as "daisy chaining" or what we call a "distributed approach".

One Power Module

Two Power Modules

Push buttons can also be wired in a distributed approach where they terminate into the flasher module instead of power module for a simpler installation.

Refer to the Level 2 document of your model for more information here.

Chevron/LED signs do not have the terminals to support other flasher modules or push buttons daisy chained to them. These must terminate to a power module or RRFB/beacon.

To maintain reliable wireless communications between power module and flashers, the recommended maximum distance between power module and the farthest flasher module is 75 ft.

Did this answer your question? Thanks for the feedback There was a problem submitting your feedback. Please try again later.

Still need help? Contact Us Contact Us