Why is the speech message not working on the Polara iNX/iDX push button?
This article details the troubleshooting steps to be taken to troubleshoot a Polara iNX/iDX speech message issue.
Product applicability
The following products are discussed in this article:
- E Series: R920-E and R820-E
- F Series: R920-F and R820-F
- G Series: SC315-G and R820-G
Systems equipped with the Polara iNX/iDX push button only.
See the checklist below for buttons that won't play the speech message:
|
Follow the instructions in the Polara Field Service app under the Update Firmware menu. Ensure you are running version 1.1.0 or newer. |
|
Set Speech Message Start Delay to 0s. Set LED Flash Behavior to Rapid Flash (for RRFBs) or Simple On/Off (for beacons/LED signs). |
|
Assign the speech message selection accordingly in the Polara Field Service app. |
|
For button wiring please see our article here. |
|
Scroll to the OUTP setting on the Carmanah Energy Management System (EMS) and ensure it is set to ALL. If it is set to NITE then the message will only work at night. |
|
Confirm there is no LED "open" or "short" fault displayed on the Carmanah EMS. Power cycle the system and try again. Check LED wiring. |
|
Adjust the Speech Message Volume settings in the Polara Field Service app. |
If your system does not have an LED load connected to it (RRFB, LED sign, circular beacon) you will need to set the OUTP setting to NLED. See our article here for more information.
The checklist above assumes you have a working system with proper system voltage.
If a firmware update is available in Polara Field Service app it is best to update all buttons at the crossing. Version 1.1.0 introduces the new standard speech message as per of MUTCD 11th Edition .